Settings on the Modbus_TCP_Slave_Device (slave)

Tab 'General'

  • Activate monitoring of the communication.

    Image Removed


    Image Added

    Warning

    The unit ID must not be used for Modbus TCP!
    This is only used for TCP/RTU gateways.

    Info

    The unit ID is only used for forwarding (gateway) to a Modbus Serial Bus.
    For TCP/IP, the MODBUS-Server is addressed by means of the IP address. In this case, the MODBUS unit ID is not used (the value 0xFF has to be used).
    For a serial connection, the Modbus devices are addressed with unit IDs from 1 to 247 (0 is used for broadcast addresses).

Tab 'I/O mapping'

  • Assign input and output variables.



...