Date: Thu, 28 Mar 2024 15:24:11 +0000 (UTC) Message-ID: <935488967.119.1711639451438@6bf000190eb4> Subject: Exported From Confluence MIME-Version: 1.0 Content-Type: multipart/related; boundary="----=_Part_118_289607722.1711639451437" ------=_Part_118_289607722.1711639451437 Content-Type: text/html; charset=UTF-8 Content-Transfer-Encoding: quoted-printable Content-Location: file:///C:/exported.html
If no target system is determined, an error message appears, "Gateway no= t configured"
=3D>
The setting of the option "Enabled 1" is necessary, since the variable "= xExec" is not used in any task and writing would therefore not work.
Activate monitoring of the communication.
The unit ID must not be used for Modbus T=
CP!
This is only used for TCP/RTU gateways.
The unit ID is only used for forwarding (gateway) to a Modbus Serial Bus=
.
For TCP/IP, the MODBUS-Server is addressed by means of the IP address. In =
this case, the MODBUS unit ID is not used (the value 0xFF has to be used).<=
br>
For a serial connection, the Modbus devices are addressed with unit IDs fr=
om 1 to 247 (0 is used for broadcast addresses).
The value changes only after transmission has been triggered manually in= the master.