The Modbus slave from the FAQ Modbus Communikation Master/Slave via Ethernet is used here.
- Create a "Standard project" and select CODESYS Control Win V3 as the device.
- Define the target system by means of the Network scan.
Insert an Ethernet adapter in the device tree and specify the interface to be used.
If a target system is not defined yet, then the error message "Gateway not configured" is displayed.
Insert a Modbus TCP Master below the Ethernet adapter in the device tree.
Insert a Modbus TCP Slave below the Modbus TCP Master in the device tree.
Insert it in the Modbus Slave Channel tab and set the properties as follows:
Adapt the POU PLC_PRG as follows:
Declaration
VAR xExec : BOOL; wMasterSend : WORD := 100; mbChannel : ModbusChannel; END_VAR
Implementation
mbChannel(slave := Modbus_TCP_Slave, xExecute := xExec);
- Assign the variable wMasterSend to the output Channel 0[0] in the tab ModbusTCPSlave I/O Mapping.
Please note, that under the ModbusTCPSlave I/O Mapping tab, the 'Always update variables' is set to 'Enabled 1' :
See also our OLH for Basic settings with Fieldbus Devices and I/O Drivers.
- Start the project and set the variable xExecute to TRUE so that the new value is passed to the slave.