Example:

bRegulatorRealState=TRUE
bDriveStartRealState=TRUE
The status- and control-word are correct
The drive can be moved via MC_MoveVelocity

Question:

With all the existing Example outputs of the system setup, why does the MC_Power.Status output stay FALSE?

Answer:

The generic CiA 402 axis requires the following bits in the status word in order to be ready for motion:

Bit 12 is not always set by every drive and therefore can prevent the axis to report Axis.SMC3_AxisReadyForMotion()=TRUE.
This, in the end, will cause MC_Power.Status to stay FALSE.

Workaround

The generic Axis can be tweaked, so that Bit 12 is not needed in position mode: