Requirement

  • Create a "Standard project" and select CODESYS Control Win V3 as the device.
  • Define the target system by means of the Network scan.



  • Open the Library Manager and add the following libraries:
    CmpApp
    CmpEventMgr
    StringUtils
    SysTypes2 Interfaces




Creating the EventHandler

  • Create a new FB named FB_EventHandler and implement the interface CmpEventMgr.ICmpEventCallback.



    The method EventCallback is created automatically with the FB:



  • Add the following variables to the FB_EventHandler:



    Section
    Column
    width7

    Declaration

    Column
    width93
    Code Block
    themeConfluence
    FUNCTION_BLOCK FB_EventHandler IMPLEMENTS ICmpEventCallback
    VAR_OUTPUT
       udiStartDone     : UDINT;
       udiStopDone      : UDINT;
       udiLogin         : UDINT;
    END_VAR
    VAR
       hEventStart      : SysTypes.RTS_IEC_HANDLE;
       hEventStop       : SysTypes.RTS_IEC_HANDLE;
       hInterfaceStart  : SysTypes.RTS_IEC_HANDLE;
       hInterfaceStop   : SysTypes.RTS_IEC_HANDLE;
       iecResult        : SysTypes.RTS_IEC_RESULT;
       itfEvtCallback   : CmpEventMgr.ICmpEventCallback;
       hEventLogin      : SysTypes.RTS_IEC_HANDLE;
       hInterfaceLogin  : SysTypes.RTS_IEC_HANDLE;
       _dwStopReason    : DWORD;
      _sAppName         : STRING;
    END_VAR







  • Adapt the method EventCallback as follows:



    Section
    Column
    width7

    Declaration

    Column
    width93
    Code Block
    themeConfluence
    METHOD EventCallback : CmpEventMgr.RTS_IEC_RESULT
    VAR_INPUT
        (*Pointer to the event parameters, see Struct EventParam*)
        pEventParam : POINTER TO CmpEventMgr.EventParam;
    END_VAR
    VAR
        pStartParam : POINTER TO EVTPARAM_CmpApp;
        pStopParam  : POINTER TO EVTPARAM_CmpAppStop;
        pLoginParam : POINTER TO EVTPARAM_CmpAppComm;
    END_VAR




    Section
    Column
    width7

    Implementation

    Column
    width93
    Code Block
    themeConfluence
    CASE pEventParam^.EventId OF
        CmpApp.EventIDs.EVT_StartDone:
            pStartParam := pEventParam^.pParameter;
            IF pStartParam <> 0 THEN
                StrCpyA(ADR(_sAppName), SIZEOF(_sAppName), ADR(pStartParam^.pApp^.szName));
            END_IF
            udiStartDone := udiStartDone + 1;
        CmpApp.EventIDs.EVT_PrepareStop:
            pStopParam := pEventParam^.pParameter;     
            IF pStopParam <> 0 THEN
                _dwStopReason := pStopParam^.ulStopReason;
            END_IF
            udiStopDone := udiStopDone + 1;
        CmpApp.EventIDs.EVT_Login:
            pLoginParam := pEventParam^.pParameter;
            udiLogin := udiLogin + 1;              
    END_CASE





  • Add the method FB_Init to the FB_EventHandler and adapt the code as follows:



    Section
    Column
    width7

    Declaration

    Column
    width93
    Code Block
    themeConfluence
    METHOD FB_Init: BOOL
    VAR_INPUT
       bInitRetains: BOOL; // TRUE: the retain variables are initialized (reset warm / reset cold)
       bInCopyCode : BOOL; // TRUE: the instance will be copied to the copy code afterward (online change)
    END_VAR




    Section
    Column
    width7

    Implementation

    Column
    width93
    Code Block
    themeConfluence
    itfEvtCallback := This^;
    hEventStart := EventOpen(CmpApp.EventIds.EVT_StartDone, CmpApp.EventIds.CMPID_CmpApp, iecResult);
    hEventStop := EventOpen(CmpApp.EventIds.EVT_PrepareStop, CmpApp.EventIds.CMPID_CmpApp, iecResult);
    hEventLogin := EventOpen(CmpApp.EventIds.EVT_Login , CmpApp.EventIds.CMPID_CmpApp, iecResult);
     
    hInterfaceStart := EventRegisterCallback(hEventStart, itfEvtCallback, iecResult);  
    hInterfaceStop := EventRegisterCallback(hEventStop, itfEvtCallback, iecResult);
    hInterfaceLogin := EventRegisterCallback(hEventLogin, itfEvtCallback, iecResult);





  • Add the method FB_Exit to the FB_EventHandler and adapt the code as follows:



    Section
    Column
    width7

    Declaration

    Column
    width93
    Code Block
    themeConfluence
    METHOD FB_Exit: BOOL
    VAR_INPUT
        bInCopyCode: BOOL;  // TRUE: the exit method is called in order to leave the instance which will be copied afterwards (online change). 
    END_VAR




    Section
    Column
    width7

    Implementation

    Column
    width93
    Code Block
    themeConfluence
    EventUnregisterCallback(hEventStart, hInterfaceStart);
    EventUnregisterCallback(hEventStop, hInterfaceStop);
    EventUnregisterCallback(hEventLogin, hInterfaceStop);
    EventClose2(hEventStart);
    EventClose2(hEventStop);
    EventClose2(hEventLogin);




Instantiating the event handler and test the functionality

  • Adapt the POU PLC_PRG as follows:



    Section
    Column
    width7

    Declaration

    Column
    width93
    Code Block
    themeConfluence
    VAR
        udiCntStart     : UDINT;
        udiCntStop      : UDINT;
        udiCntLogin     : UDINT;
        fbEventHandler  : FB_EventHandler;
    END_VAR




    Section
    Column
    width7

    Implementation

    Column
    width93
    Code Block
    themeConfluence
    fbEventHandler(udiStartDone => udiCntStart, udiStopDone => udiCntStop, udiLogin => udiCntLogin);







  • Download the project to the controller and start it.
    When logging in/out and starting the project, the counters are incremented.