Versions Compared

Key

  • This line was added.
  • This line was removed.
  • Formatting was changed.

...

  • Enter the IP address of the device.

Note

The option Check Major Revision can be deactivated in order to avoid errors.


Image Modified

Tab Connections

  • Through the EDS file a standard connection is created with the connection path 20 04 2C 65 2C 68.



    From the Wago manual (WAGO Assembly Instances) it can be seen that 0x65 (101) in the connection path means the following: 0x65 (101) → for analog and digital output data Since we are only using a digital output terminal, you need to change this value to 0x66 (102): 0x66 (102) → for digital output data Also, change the value 0x68 (104) → for analog and digital input data with status byte to 0x69 (105) for digital input data with status byte. This produces the following connection path: 20 04 2C 66 2C 69 To be able to change the connection path you have to delete the existing connection and add a new one. Set the new connection to generic connection (freely configurable) and the settings for the connection path to user-defined path. In addition, make the following settings:

...